Publication 1757-IN500A-EN-P - September 2002

Firmware Maintenance Procedures 7-3

1784-PCIC Firmware
Installation

If your 1784-PCIC firmware has not been updated for ProcessLogix R500.1,
this procedure must be followed to use the 1784-PCIC in R500.1.

Starting Network Tools Application

If this is the first time you have used Network Tools on this PC, refer
to Making First Time Network Tools Settings on page 8-8
and then continue
with this procedure beginning at Step 6.

1. Click Start

Run.

2. Enter this command:

>ntools -c -u<

3. Click OK to launch the Network Tools application.

4. Click OK to acknowledge the warning about monitoring through

Control Builder.

5. Click Resume

to initiate network scan.

Updating the 1784-PCIC Firmware

6. Click the desired PCIC icon under the Desktop tree and wait for the

card details to appear in the Detail pane.

7. Check the firmware revision shown in the Name field.

• If the firmware is 3.6.38, you do not need to update the firmware.
• If the firmware is not 3.6.38 go to Step 8.

8. Click the firmware

to initiate the firmware update.

9. Click Yes to acknowledge the Warning prompt.

10. Navigate to the directory:


C:\Honeywell\TPS50\System\Firmware\1784-PCIC\3_6_38

11. Click the 2MnBtPcic3x.nvs file so it appears in the File name entry field.

12. Click Open to start the firmware load and click Yes to confirm.

IMPORTANT

You must have the 1784-PCIC configured in RSLinx. Refer
to Configuring RSLinx Drivers for ControlNet Supervisory
Network on page 3-15
to configure the 1784-PCIC drivers
in RSLinx.