Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual

Page 209

Advertising
background image

Publication 1757-IN500A-EN-P - September 2002

Supplementary Procedures 8-11

9. In the Local Chassis tab, adjust the number in the scroll box to match

the number of slots in your local chassis.

10. If your system includes a remote chassis, go to Step 11. Otherwise, go to

Step 15.

11. Click the Remote Chassis 1 tab.

12. Check the Check here if... installed checkbox.

13. Adjust the numbers in the appropriate scroll box to match the following

data about your remote chassis.
a. Number of slots in your remote chassis.
b. Network Address (MAC ID) of CNB in your remote chassis.

The assigned MAC ID is repeatedly shown in the LED display on the
CNB module in the format A#NN, where NN is the Network
Address. For example, a display of A#03 means the CNB Network
Address is 3.

c. Slot number where downlink CNB is installed in your local chassis.

This is the CNB that is cable connected to the uplink CNB in your
remote chassis.

Advertising