Publication 1757-IN500A-EN-P - September 2002

Additional Redundant Server Procedures 6-19

The message Password accepted should appear in the message zone.
If it does not repeat steps 6 and 7.

Only systems using operator based security and Control Builder are
affected by this change. The mngr operator account is different than the
Windows mngr user account. Navigate in Knowledge Builder to
Administration and Startup Guide for more information before changing
the password of the Windows mngr user account.

8. Click Start

Programs

ProcessLogix Engineering Tools

DB Admin.

9. Click the

+

sign to expand DbAdmin.

10. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.
b. Enter the appropriate Password.
c. Enter SERVERB in the Server Name field.
d. Choose Classic Server Security in the Domain Name drop down box.

11. Click OK.

12. Click the

+

sign to expand the ProcessLogix Node.

13. Click Admin Tasks.

14. Click Disable Replication.

15. Click OK at the Disabled Database Replication prompt.

16. Click Recover Secondary Database.

a. Click Yes to recover Secondary Database.
b. Click OK at the Successfully Recovered Secondary Database prompt.

17. Click Enable Replication.

a. Click Yes to proceed.
b. Click OK at the Successfully Enabled Database Replication prompt.

18. Close DBAdmin.