6-12 Additional Redundant Server Procedures
15. Click OK to initiate the download.
16. Click OK to acknowledge the successful download prompt and close
the dialog box.
17. Click File
⇒
Exit to close Quick Builder.
Setting Up Station on
SERVERA
1. On SERVERA, click Start
⇒
Programs
⇒
ProcessLogix Server
⇒
Station.
2. Click Cancel at the Unable to connect prompt, if applicable.
3. Click Station
⇒
Connect to call up the Station Connect dialog box.
4. Click New Connection.
5. On the Connection tab, make these entries to have the Station point to
SERVERB (PLX1B):
a. In the Server field, enter or Browse to the Secondary Server name,
SERVERB.
b. Select the Station type as Static Station.
c. Enter >1< as the Static Station Number and click Advanced.
d. Check the Auxiliary setup file checkbox.
e. Click Browse and navigate to:
C:\Honeywell\Client\Station\default.stn and click Open.
IMPORTANT
You must indicate the full path to the .stn file.