Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 93
Publication 1757-IN500A-EN-P - September 2002
ProcessLogix Server Upgrade Procedures 4-5
b. Enter >mngr1< as the default Password.
c. Enter >localhost< in the Server Name field.
4. Click OK.
5. Click File
⇒
Export.
6. Click Browse to set the Directory Path to C:\Data\ExportDB.
7. Click Select All.
a. Depending on the size of your database, this may take several
minutes. It is recommended that you do not export the examples.
New examples are provided with R500.1.
b. To deselect an item, hold Ctrl and click each item.
c. Deselect the following Point Names:
example_cascade
example_motor
example_pid
example_scm
pidloop
8. Click Export.
Depending on the size of your database, this step may take several
minutes to several hours.
9. When completed, close the Export Window (if it did not automatically
close).
10. Close Control Builder.