Supplementary Procedures 8-25

Adding 1757-PLX52
Controller Redundancy to
R500.1 Non-Redundant
1757-PLX52 Controller
Configurations

Deleting a Non-Redundant 1757-PLX52 and Unassigning its
Contents

Use the following procedure to save your existing database and delete it from
the existing non-redundant 1757-PLX52 Controller.

1. Start Control Builder.

2. Close any open Control Module and/or Sequential Control Module.

3. In Monitoring tab, click the plus sign in the tree root path to the

non-redundant CPM being made redundant to display the CEE folder
icon.

4. Click the CEE folder icon.

5. Click Tools

Upload with Contents to upload the existing controller

database.

6. Click Continue.

This may take considerable time to complete, depending on the amount
of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.

7. Click the CEE folder icon.

8. Click Tools

Update with Contents (to Project) to save the existing

controller database.

9. Click Continue.

This may take considerable time to complete, depending on the amount
of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.

10. Click the CEE folder icon.

ATTENTION

!

Be certain that your process is off control before you begin
any upgrade procedure. This means the 1757-PLX52
should be in the Idle state.