PROFIBUS DP Capacity and Topology Specifications

The following PROFIBUS specifications are independent of the interface to
ProcessLogix:

• PROFIBUS DP supports a maximum of 126 station addresses,

including, masters, slaves and active repeaters.

• The maximum number of entries in the PBIM configuration table is

100.

Maximum number CN2FFs per 1757-PLX52

• Each Linking Device counts as 1 I/O unit in the 64 I/O units per 1757-PLX52

calculation above.

8

Not Supported

Maximum number CN2FFs per Non-Redundant Server

8

Not Supported

Maximum number CN2FFs per Redundant Server (NI-FBUS Service and NI Configurator
must be run on the Backup Server only)

48

Not Supported

Maximum number CN2FFs per NI Configurator Project

1

Not Supported

Maximum Number of H1 segments per CN2FF

2

Not Supported

Maximum number of Foundation Fieldbus Devices per H1 segment connected to a
CN2FF.

10

Not Supported

1757-FIM Related Only

50ms CEE

5ms CEE

Maximum number 1757-FIM’s per 1757-PLX52

• Each 1757-FIM counts as 3 I/O units in the 64 I/O units per 1757-PLX52

calculation above.

21

Not supported

Maximum number 1757-FIMs per Server (Redundant or Non-Redundant)

100

Not Supported

Maximum number of H1 segments per 1757-FIM

2

Not supported

Maximum number of FF Devices per H1 segments connected to a 1757-FIM.
(other constraints may be encountered before this constraint)

16

Not Supported

Configurable Values for FF function block Execution Periods. (Since 250 ms period is not
compatible with the CM’s 200 ms period, it should only be used for control if the entire
loop is resident on a Fieldbus link.)

250, 500, 1000,
2000, 4000 ms

Not Supported

Profibus Interface-Related Only

50 ms CEE

5 ms CEE

Maximum number of PFB Modules per 1757-PLX52

10

2

Maximum number of PFB Modules per downlink CNB (based on update rate, 25ms
default)

4 @ 25 ms
2 @ 12.5 ms

Not Supported

Table 11.S I/O Module Capacity