Exporting the processlogix server database, Exporting the processlogix server database -8 – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual

Page 96

Advertising
background image

Publication 1757-IN500A-EN-P - September 2002

4-8 ProcessLogix Server Upgrade Procedures

Exporting the ProcessLogix Server Database

If you have a Redundant Server pair, complete this procedure on SERVERA
only.

1. Logon to the R320.0 system as plx_user.

2. Click Start

Run.

3. Enter this command:


>cmd<


and click OK to open the DOS window.

4. At the DOS prompt, enter the following command:


>hscserver /unload /y<


and press <Enter>.

5. Enter the following command:

xcopy C:\Honeywell\server\data\*.* C:\Data\Server\backup /E

and press <Enter>.

6. If necessary, enter >D< to specify that backup is a directory.

7. Wait until the C:\ prompt appears and close the DOS window.

ATTENTION

!

Before exporting the ProcessLogix Server Database, you
must exit all ProcessLogix applications and stop all
ProcessLogix services. Refer to Stopping ProcessLogix
Applications and Services on page 8-1.

If you have redundant servers, you must complete this
procedure on the SERVERB node first. Then complete
the entire procedure again for the SERVERA node.

Advertising