Publication 1757-IN500A-EN-P - September 2002

Supplementary Procedures 8-27

Installing and connecting Redundant Chassis Pair (RCP)
Hardware

Refer to the following data in Knowledge Builder for general information
about Controller redundancy and how to install and connect the 1757-PLX52,
1757-SRM Redundancy Module (SRM), and 1756-CNBR redundant
ControlNet Bridge module (CNB).

• Navigate in Knowledge Builder to Control Builder Components

Theory

Controller Redundancy Functionality before upgrading to a

Redundant Chassis Pair for general information about Controller
redundancy and related terminology.

• Navigate in Knowledge Builder to Control Hardware Installation Guide

Controller Module Installation and Removal for information on installing

the 1757-PLX52 module.

• Navigate in Knowledge Builder to Control Hardware Installation Guide

Redundancy Module Installation and Removal for information on installing

the 1757-SRM module.

• Navigate in Knowledge Builder to Control Hardware Installation Guide

ControlNet Communication Module Installation and Removal for

information on installing the 1756-CNB module.

Updating Firmware Revision Levels

Refer to Upgrading Hardware Component Firmware on page 7-4 to
check/upgrade 1757-PLX52, 1756-CNB, and 1757-SRM firmware.

Creating a Redundant 1757-PLX52

1. Create redundant CPMs

Navigate in Knowledge Builder to Control Building Guide

Hardware

Module Creation

Creating a Control Processor Module for more information

about configuring a redundant 1757-PLX52 in Control Builder.

IMPORTANT

Stop! It is essential that you check the firmware revision
levels for ALL ProcessLogix hardware components after a
ProcessLogix software installation.

Do not proceed until you have upgraded the firmware.