Control network capacity – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual

Page 251

Advertising
background image

Publication 1757-IN500A-EN-P - September 2002

Performance and Capacity Specifications 11-11

Controller and
Communications Capacity
and Performance

Control Network Capacity

System Communications Load Philosophy and Guidelines

The ProcessLogix System is designed with certain patterns of communications
in mind. Being aware of the intended traffic flows will help the application
engineers insure that the application realizes the highest usage from the
system’s architectural capabilities.

The basic concept is shown in the following hierarchical diagram. It shows
four levels of networking: Plant Information, Supervisory, I/O, and Device. It
also includes four levels of networking nodes: Application stations (like

Table 11.J Process Control Network Specifications

Supervisory Process Control Network

Network Media

Ethernet

ControlNet

Supervisory Networks per ProcessLogix Server

(1 PCIC card per Server)
Mixed Supervisory ControlNet & Ethernet on the same Server is
not supported.

1 non-redundant network
serviced by 1 redundant or
non-redundant Server

1 redundant or non-redundant
network serviced by 1 redundant
or non-redundant Server

Total ControlNet connections Limit

(1)

N/A

127

Allowable Combinations of Controllers * per Server

Up to 10 non-redundant only

Up to 10 redundant or
non-redundant in any
combination

Maximum Number of Nodes allowed including Controllers,
Servers and FIM-only chassis.

12

• Only qualified for redundant

Servers +10 non-redundant
controllers

• FIMs are not supported on a

Supervisory Ethernet system
in any configuration

24

Data Transmission Rate

10 Mbits/sec

5 Mbit/sec

Media Redundancy

Non-redundant only

Single cable or redundant media
operation supported.

Controller Definitions including PLCs
Multiple 1757-PLX52s per chassis are NOT supported. However, a
non-redundant 1757-PLX52 can reside in the same chassis as a
Logix 5550.
PLCs only count as controllers when SCADA connections are
defined against the PLC.

Non-Redundant:

• 1 1757-PLX52

• 1 Logix5550

• 1 PLC5/C or E

• 1 SLC (Ethernet only)

Redundant:

• 2 1757-PLX52s in a Chassis

Pair with 2 1757-SRMs

• 2 1756-5555s in a chassis pair

with 2 1757-SRMs

(1)

The CPM and FIM use 1 PCIC connection from the Server regardless of whether they reside on a Supervisory or I/O ControlNet. PLCs should be limited to 2 connections if

configured as SCADA controllers via RSLinx.