Publication 1757-IN500A-EN-P - September 2002

8-10 Supplementary Procedures

5. Do the following in the Options tab.

a. Enter >2< in the field for Delay between scans (seconds).
b. Select the Periodic (automatic) option.

This means automatic scans are made periodically with the specified
delay between scans.

c. Check Enable Module Version/Revision Checking.

This turns ON the automatic firmware version/revision detection
function. This means Network Tools automatically detects any
incompatible firmware in a given module and shows the module’s
firmware indication in Red instead of Green on the module’s graphic
representation.

d. Check Enable ControlNet Parameter Checking.

This turns on the function for checking ControlNet parameter
settings.

6. Click OK to close the dialog box.

7. Click Resume

to initiate network scan.

8. When network nodes appear under the Desktop tree icon, click the first

CNB or Ethernet driver icon to call up the settings dialog box.

You only have to make these settings on the initial scan of the system.
However, you can access the settings at any time by clicking the CNB or
ENET icon and then clicking Settings

.