Supplementary Procedures 8-13

Installing and Running
NetShield with
ProcessLogix

Background

Problems with starting up and synchronizing Servers and crashing of
NetShield components can result from running the components concurrently
with the ProcessLogix software unless NetShield is specifically installed and
run as described in this section.

The problems noted above have occurred with version 4.5 of Network
Associates (formerly known as McAfee) NetShield, when running
automatically upon startup or during file access.

If the NetShield program is already installed on your ProcessLogix Server, go
to the next section to remove it. Otherwise, go to the section entitled Installing
NetShield and configuring directories for scan exclusion.

Removing Existing NetShield Installation

If NetShield is currently installed on the ProcessLogix Server, use the
following procedure to remove it.

1. Click Start

Settings

Control Panel.

2. Double-click the Add/Remove Programs icon.

3. Select NetShield and click Remove.

4. Click Yes to confirm the action and follow the on-screen instructions

on the Uninstall Wizard to remove the NetShield program.

5. Click Yes to restart the PC if prompted.

The PC must be restarted before continuing with the next section.

IMPORTANT

If you need to run the Network Associates NetShield 4.5
for NT and 2000 application on a ProcessLogix Server, you
must install and run the application as described in this
section.