4-22 ProcessLogix Server Upgrade Procedures
Saving R400.0 Data to a
Remote PC
Networking an R400.0 Server to a Remote PC
Use the following procedure to map a drive to a remote PC.
1. Logon to the R400.0 Server as ps_user.
2. Click Start
⇒
Run.
3. Enter this command:
>cmd<
and click OK to open the DOS window.
4. Enter this command:
>NET USE T: \\STN01\C$
/user:ps_user<
(where STN01 is the remote PC name and ps_user is the user currently
logged on to STN01.)
and press <Enter>.
5. Open Windows Explorer and confirm that the T: drive exists.
Transferring Data
1. If you have a non-redundant server:
a. Enter this command:
xcopy C:\Data\*.* T:\R400Data /E
and press <Enter>.
b. If necessary, enter >D< to specify that R400Data is a directory.
2. If you have a redundant Server pair,