9-17

9.9.1

Selecting the Logic and Reference Source

Parameters 89 (Logic Source Sel) and 90 (Ref Source Sel) are
used to select the drive control and speed reference sources. These
parameters are grouped in the Control Src Select menu. See figure
9.15.

Both of these parameters can also be accessed individually through
the Parameters menu.

Refer to chapter 12 for a description of the parameters.

9.9.2

Starting the Drive

When the OIM is the selected control source, pressing

issues

a start command to the drive.

9.9.3

Stopping the Drive

Pressing

will issue a stop command to the drive.

Important: Stop commands from any attached OIM will always be

enabled.

!

ATTENTION: Removing and replacing the LCD OIM
while the drive is running may cause an abrupt speed
change if the LCD OIM is the selected reference
source, but is not the selected control source. The
drive will ramp to the reference level provided by the
OIM at the rate specified in Accel Time 1 (140), Accel
Time 2 (141), Decel Time 1 (142) and Decel Time 2
(143). Be aware that an abrupt speed change may
occur depending upon the new reference level and
the rate specified in these parameters. Failure to
observe this precaution could result in bodily injury.

Figure 9.15 – Selecting the Control and Reference Source

Monitor

Lang

P0: SP600

Auto

Stopped

Main Menu

Control Src Sel

Highlight Control Src Sel icon

Control Src Sel:

Speed Ref A Sel

Logic Source Sel

>>