Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 243

Advertising
background image

Troubleshooting the Drive

13-11

13.4.3 Fault Descriptions and Corrective Actions

Table 13.6 describes drive faults and corrective actions. It also
indicates if the fault is:

➀ Auto-resettable
➁ Non-resettable
➂ User-configurable

Table 13.6 – Fault Descriptions and Corrective Actions

Fault

No

.

Ty

p

e

Description

Action

Analog In
Loss

29

An analog input is
configured to fault on
signal loss. A signal loss
has occurred.

Configure with Anlg In
1, 2 Loss (324, 327).

1. Check parameters.

2. Check for broken/loose

connections at inputs.

Anlg Cal
Chksum

108

The checksum read
from the analog
calibration data does
not match the checksum
calculated.

Replace drive.

Auto Rstrt
Tries

33

Drive unsuccessfully
attempted to reset a
fault and resume
running for the
programmed number of
Auto Rstrt Tries (174).

Enable/disable with
Fault Config 1 (238).

Correct the cause of the
fault and manually clear.

AutoTune
Aborted

80

The autotune procedure
was canceled by the
user.

Restart procedure.

DB
Resistance

69

Resistance of the
internal DB resistor is
out of range.

Replace resistor.

Advertising