Parameter Descriptions

12-13

.

Sets the highest voltage the drive will output.

Sets the maximum allowable frequency the drive will output. Note
that is not maximum speed, which is set in parameter 82. Refer to
figure 12.4.

Maximum Speed (82) + Overspeed Limit (83) must be

≤ Maximum Freq (55).

Figure 12.3 – Fan/Pump Curve

Maximum Voltage

Maximum
Frequency

Base Voltage

(Nameplate)

Base Frequency

(Nameplate)

Run Boost

54

Maximum Voltage

Range:

(Rated Volts x 0.25) to Rated Volts [0.1 VAC]

Default:

Drive Rated Volts

Access:

2

Path: Motor Control>Torq Attributes

See also:

55

Maximum Freq

Range:

5.0 to 400.0 Hz [0.1 Hz]

Default:

130.0 Hz

Access:

2

Path: Motor Control>Torq Attributes

See also:

82, 83

Figure 12.4 – Speed Limits

Allowable Output Frequency Range

Bus Regulation or Current Limit

V

o

l

t

a

g

e

Frequency

Allowable Output Frequency Range

Normal Operation

Allowable Reference Frequency Range

Frequency Trim due to
Speed Control Mode

Max Volts

Motor Volts

Break Volts

Start Boost

Run

0

Min

Speed

Motor

Hz

Max

Speed

Output

Freq Limit

Max
Freq

Break

Frequency

Overspeed

Limit