Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 170

Advertising
background image

12-40

SP600 AC Drive User Manual

.

Selects the active stop mode. Stop Mode A is active unless Stop
Mode B is selected by a digital input. This function allows the user to
switch between two possible stop modes using an external logic
signal. Refer to figure 12.18.

0 = Coast: When Stop Mode A (155) is set to Coast, the drive
acknowledges the Stop command by shutting off the output
transistors and releasing control of the motor. The
load/motor will coast or free spin until the mechanical energy is
dissipated.

155
156

Stop Mode A
Stop Mode B

Range:

0 = Coast
1 = Ramp
2 = Ramp to Hold
3 = DC Brake

Default:

155: 1 = Ramp
156: 0 = Coast

Access:

155=0
156=2

Path: Dynamic Control>Stop/Brake Modes

See also:

157-159, 361-366

!

ATTENTION: The user must provide an external,
hardwired emergency stop circuit outside of the drive
circuitry. This circuit must disable the system in case
of improper operation. Uncontrolled machine
operation may result if this procedure is not followed.
Failure to observe this precaution could result in
bodily injury.

Figure 12.18 – Selecting Stop Mode B

Dig In #

Dig In #

Dig In #

Dig In #

+24 V

Stop Mode

B

Refer to parameters 361- 366.