Parameter Descriptions
12-17
Sets the voltage boost level for starting and acceleration when 
Custom V/Hz mode is selected in Torque Perf Mode (53). After 
acceleration has stopped, the output volts/hertz is set by the steady 
state operating curve. See figure 12.7.
Sets the boost level for steady state or deceleration when Fan/Pmp 
V/Hz or Custom V/Hz modes are selected in Torque Perf Mode (53). 
This boost level applies in the range from zero to Break Frequency 
(72). See figure 12.7.
Sets the voltage the drive outputs at Break Frequency (72) and 
defines the volts per hertz ratio at the break frequency. Applies only 
if Fan/Pump or Custom V/Hz is selected in parameter 53 (Torque 
Perf Mode). See figure 12.7.
Sets the frequency the drive will output at Break Voltage (71). 
Applies only if Fan/Pump or Custom V/Hz is selected in parameter 
53 (Torque Perf Mode). See figure 12.7.
69
Start/Acc Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Motor NP Volts x 0.25
Access:
2
Path: Motor Control>Volts per Hertz
See also:
53, 70, 83
70
Run Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Motor HP Volts x 0.25
Access:
2
Path: Motor Control>Volts per Hertz
See also:
53, 69, 83
71
Break Voltage
Range:
0.0 to Motor NP Volts [0.1 VAC]
Default:
Motor NP Volts x 0.25
Access:
2
Path: Motor Control>Volts per Hertz
See also:
53, 72, 83
72
Break Frequency
Range:
0.0 to 400.0 Hz
Default:
Motor NP Freq
Access:
2
Path: Motor Control>Volts per Hertz
See also:
53, 71, 83