Example:

Calculate the maximum power of a 5 HP, 460V motor connected to a 480V rated
drive supplied with 342V Actual Line Voltage input.

• Actual Line Voltage / Nominal Motor Voltage = 342/460 x 100% = 74.3%

• 74.3%

× 5 HP = 3.7 HP

• 74.3%

× 60 Hz = 44.6 Hz

At 342V Actual Line Voltage, the maximum power the 5 HP, 460V motor can
produce is 3.7 HP at 44.6 Hz.

HP

@ Motor (Drive Output)

Actual Line Voltage (Drive Input)

Full Power Range

Drive Operating Range

Nominal Motor Voltage -10%

Nominal Motor Voltage

Derated Power Range

No Drive

Output

Drive Rated Voltage

Drive Rated Voltage +10%

5 HP

3.7 HP

HP

@ Motor (Drive Output)

Actual Line Voltage (Drive Input)

342V

460V

No Drive

Output

480V

528V