Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 90

Advertising
background image

7-8

SP600 AC Drive User Manual

Table 7.3 – Parameter Configuration for Figure 7.1 Wiring Example

Param.

Number

Description

Value

Default

89

Logic Source Sel

Terminal Block

Local OIM

90

Spd Ref A

Anlg #1

Local OIM

91

Spd Ref A Hi

60 Hz

Same as Max Speed

92

Spd Ref A Lo

0 Hz

0.0 Hz

96

TB Man Ref

Anlg #2

Anlg #2

97

TB Man Ref Hi

60 Hz

Same as Max Speed

98

TB Man Ref Lo

0 Hz

0.0 Hz

320

Analog Conf

xxx.xx01

xxx.xx01

322

Anlg In 1 Hi

20 mA

20 mA

323

Anlg In 1 Lo

4 mA

4 mA

325

Anlg In 2 Hi

10 V

10 V

326

Anlg In 2 Lo

0 V

0 V

361

Dig In 1 Sel

Stop

Stop

362

Dig In 2 Sel

Start

Start

363

Dig In 3 Sel

Function Loss

Function Loss

364

Dig In 4 Sel

Jog

Jog

365

Dig In 5 Sel

Manual

Manual

366

Dig In 6 Sel

Speed Sel 1

Speed Sel 1

Advertising