12-54

SP600 AC Drive User Manual

Enables a feature to save the present frequency reference value
issued by the OIM. This value is saved to drive memory on power
loss. The value is then restored to the OIM on power up.

Enables/disables a feature to automatically load the present auto
frequency reference value into the OIM when Manual is selected.
This allows smooth speed transition from Auto to Manual; you can
then adjust the manual speed setpoint starting from the transferred
Auto speed level.

0 = Disabled: No preload of the Auto speed setpoint into the
manual setpoint. In this case, the motor reference will switch
automatically to the internal Manual setpoint.

1 = Enabled: The Manual setpoint will be loaded with the present
running speed.

192

Save OIM Ref

Range:

See figure 12.25

Default:

See figure 12.25

Access:

2

Path: Utility>OIM Ref Config

See also:

Figure 12.25 – Save OIM Ref (192)

x

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

Nibble 1

Nibble 2

Nibble 3

Nibble 4

193

Man Ref Preload

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

Access:

2

Path: Utility>OIM Ref Config

See also:

320 - 327, 361 - 366