Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 184
 
12-54
SP600 AC Drive User Manual
Enables a feature to save the present frequency reference value 
issued by the OIM. This value is saved to drive memory on power 
loss. The value is then restored to the OIM on power up.
Enables/disables a feature to automatically load the present auto 
frequency reference value into the OIM when Manual is selected. 
This allows smooth speed transition from Auto to Manual; you can 
then adjust the manual speed setpoint starting from the transferred 
Auto speed level. 
0 = Disabled: No preload of the Auto speed setpoint into the 
manual setpoint. In this case, the motor reference will switch 
automatically to the internal Manual setpoint.
1 = Enabled: The Manual setpoint will be loaded with the present 
running speed.
192
Save OIM Ref
Range:
See figure 12.25
Default:
See figure 12.25
Access:
2
Path: Utility>OIM Ref Config
See also:
Figure 12.25 – Save OIM Ref (192)
x
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Save 
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At P
owr Do
wn
Nibble 1
Nibble 2
Nibble 3
Nibble 4
193
Man Ref Preload
Range:
0 = Disabled
1 = Enabled
Default:
1 = Enabled
Access:
2
Path: Utility>OIM Ref Config
See also:
320 - 327, 361 - 366