Parameter Descriptions

12-57

Loads a previously saved set of parameter values from a selected
user set location in the drive’s non-volatile memory to active drive
memory. After data is successfully transferred, the value returns to
0.

The drive has the capability of saving up to three complete sets of
drive parameters (configurations). These sets can be restored to
drive memory for runtime operation.

An F-Key on the LCD OIM can be configured for this function. Refer
to chapter 9.

Saves the parameter values in active drive memory to a user set in
drive non-volatile memory. After the data if successfully transferred,
the value returns to 0.

An F-Key on the LCD OIM can be configured for this function. Refer
to chapter 9.

Resets the selected meter to zero.

1 = MWh: Resets Elapsed MWh (9) to zero.

2 = Elapsed Time: Resets Elapsed Run Time (10) to zero.

198

Load Frm Usr Set

Range:

0 = Ready
1 = User Set 1
2 = User Set 2
3 = User Set 3

Default:

0 = Ready

Access:

1

Path: Utility>Drive Memory

See also:

199

199

Save To User Set

Range:

0 = Ready
1 = User Set 1
2 = User Set 2
3 = User Set 3

Default:

0 = Ready

Access:

1

Path: Utility>Drive Memory

See also:

198

200

Reset Meters

Range:

0 = Ready
1 = MWh
2 = Elapsed Time

Default:

0 = Ready

Access:

1

Path: Utility>Drive Memory

See also: