Technical Specifications
A-3
Important:
Removing the adhesive label from the drive changes
the NEMA enclosure rating from Type 1 Enclosed to
Open Type.
Table A.3 – Environment
Altitude
1000 m (3300 ft) max. without derating
Ambient Operating Temperature
Without Derating:
Open Type, IP20, IP54, NEMA
Type 1, and Flange Mount:
IP66 and NEMA Type 4X/12:
0 to 50°C (32 to 122°F)
0 to 40°C (32 to 104°F)
Storage Temperature (all const.) –40 to 70
°
C (158
°
F)
Atmosphere
Important:
Drive must not be installed
in an area where the
ambient atmosphere
contains volatile or
corrosive gas, vapors, or
dust. If the drive is not
going to be installed for a
period of time, it must be
stored in an area where it
will not be exposed to a
corrosive atmosphere.
Relative Humidity
5 to 95% non-condensing
Shock
15G peak for 11ms duration (
±1.0 ms)
Vibration
0.152 mm (0.006 in.) displacement, 1G
peak