12-22

SP600 AC Drive User Manual

Important:

The drive is shipped from the factory configured for
local OIM (keypad) control. For drive control from the
terminal block inputs, Logic Source Sel (89) must be
set to 0 = Terminal Blk.

Logic Source Sel (89) defines the control source for the following
logic commands (see figure 12.9):

0 = Terminal Blk: Hardware I/O control

1 = Local OIM: Drive-mounted OIM

2 = DPI Port 2: DIN connector DPI port

3 = DPI Port 3: DIN port 2 split with option cable

4 = Reserved

5 = Network: Communications interface

6 = Reserved

7 = All Ports: All control sources active

Important:

Asserting the terminal block input assigned to the OIM
control function overrides parameter 89. You can
switch control from the terminal block to the OIM by
configuring Digital In

x

Sel (361-366) to the OIM

control function. This switching will affect logic control
and the speed reference source. Refer to the
parameter 361-366 description for detail.

• Start

• Jog

• Clear Faults

• Direction

• Stop

• Run

Figure 12.9 – Logic Source Sel (89)

Comm

Module

Control

Functions

RUN

START

JOG

DIRECTION

CLEAR
FAULTS

STOP

Logic Source

Sel (89)

Terminal

Block

Local OIM

DPI

Port 3

Network

Remote

OIM

Note: All Ports allows
parallel control of
devices.

DPI

Port 2

Remote

OIM