Parameter Descriptions

12-97

23 = Input 3 Link: Outputs the state of digital input 3.

24 = Input 4 Link: Outputs the state of digital input 4.

25 = Input 5 Link: Outputs the state of digital input 5.

26 = Input 6 Link: Outputs the state of digital input 6.

27 = TB in Manual: Terminal block has manual reference control.

Sets the relay activation level for options 10-15 in parameter 380
(Digital Out1 Sel). Units are assumed to match the selection of
parameter 380. (i.e., At Freq = Hz, At Torque = Amps).

Sets the on delay time for the digital outputs. This is the time
between the occurrence of a condition and activation of the relay.

Sets the off delay time for the digital outputs. This is the time
between the disappearance of a condition and de-activation of the
relay.

381

Dig Out1 Level

Range:

0.0 to 819.2 [0.1]

Default:

0.0

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also:

380

382

Dig Out1 OnTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Outputs>Digital Outputs

See also:

380

383

Dig Out1 OffTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Outputs>Digital Outputs

See also:

380

Figure 12.53 – Dig Out1 OffTime (383)

Comparator

Delay
Timer

Output

Frequency

(380)

Dig Out1

Level (381)

Dig Out1

OnTime

(382)

Relay Out1

(Term 11, 12, 13)

Dig Out1

OffTime

(383)