6 common symptoms and corrective actions – Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 250

Advertising
background image

13-18

SP600 AC Drive User Manual

13.6

Common Symptoms and Corrective Actions

Table 13.9 – Drive Does Not Start From Start, Run, or Jog Inputs Wired to the

Terminal Block

Indication(s)

Cause(s)

Corrective Action

Flashing red
Ready LED.

Drive is faulted.

Clear fault:

• Press OIM Stop key if

that OIM is control
source.

• Cycle power.

• Set Fault Clear (240) to

1.

• Toggle terminal block

stop or terminal block
reset digital input if
terminal block is the
control source.

Incorrect operation
from the terminal
block.

Incorrect input wiring.

• 2-wire control requires

Run, Run Forward, or
Run Reverse input(s).

• 3-wire control requires

Start and Stop inputs

• Jumper from terminal 7

to 8 is required.

Wire inputs correctly
and/or install jumper.

Incorrect digital input
programming.

• Mutually exclusive

choices have been
made.

• 2-wire and 3-wire

programming may be
conflicting.

• Exclusive functions (i.e.,

direction control) may
have multiple inputs
configured.

• Stop if factory default and

is not wired or is open.

• Start or Run

programming may be
missing.

Program Digital In”x” Sel
(361-366) for correct
inputs.

Logic Source Sel is not set
to Terminal Blk.

Set Logic Source Sel to
Terminal Blk.

Advertising