Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 156

Advertising
background image

12-26

SP600 AC Drive User Manual

Analog input reference scaling. Scales the lower value of the TB
Man Ref Sel (96) selection when the source is an analog input.
Parameter 98 should be set in conjunction with Analog In 1 Lo (323)
or Analog In 2 Lo (326) depending on the appropriate analog input
used. See figure 12.51.

Sets the output frequency when a jog command is issued. The jog
function can be activated from the terminal block or OIM keypad.

Provides an internal fixed speed command value when
Speed Ref A is set to one of the Preset Speed (1-7) internal
references. Alternatively, one of the internal preset speed setpoint
values can be selected via logic control if any of the Digital In

x

Sel

(361-366) are configured to be Speed Sel 1, 2, or 3.

98

TB Man Ref Lo

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

1

Path: Speed Command>Speed References

See also:

96

100

Jog Speed

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

10.0 Hz

Access:

0

Path: Speed Command>Discrete Speeds

See also:

101
102
103
104
105
106
107

Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

See table 12.2

Access:

101=0
102 -107=2

Path: Speed Command>Discrete Speeds

See also: 90

Table 12.2 – Default Values for Preset Speeds 1-7

Parameter No.

Parameter Name

Default

101

Preset Speed 1

5.0 Hz

102

Preset Speed 2

10.0 Hz

103

Preset Speed 3

20.0 Hz

104

Preset Speed 4

30.0 Hz

105

Preset Speed 5

40.0 Hz

106

Preset Speed 6

50.0 Hz

107

Preset Speed 7

60.0 Hz