Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 242

Advertising
background image

13-10

SP600 AC Drive User Manual

in PowerUp Marker to determine when the fault occurred relative to
the last drive power up.

The time stamp is cleared when the fault queue is cleared.

Refer to section 13.8.1 for information on accessing the fault queue
using the LCD OIM. Refer to instruction manual D2-3488 for
information on accessing the fault queue using VS Utilities software.

13.4.2 Clearing Faults

A fault condition can be cleared by the following:

Step 1. Press

or any F-Key to acknowledge the fault and

remove the fault pop-up from the LCD OIM screen.

Step 2. Address the condition that caused the fault. The cause must

be corrected before the fault can be cleared.

Step 3. After corrective action has been taken, clear the fault using

one of the following:

• Set Fault Clear (240) = 1 (Clear Faults).

• Press F1 (Cflt) from the fault queue screen.

• Issue a Stop-Clear Faults command from the control

source.

Resetting faults will clear the faulted status indication. If any fault
condition still exists, the fault will be latched and another entry made
in the fault queue.

Note that performing a fault reset does not clear the fault queue.
Clearing the fault queue is a separate action. See the Fault Clear
(240) parameter description.