Safety Ground - PE
This is the safety ground for the drive that is required by code. This 
point must be connected to adjacent building steel (girder, joist), a 
floor ground rod or bus bar (see figures 5.2 and 5.3). Grounding 
points must comply with national and local industrial safety 
regulations and/or electrical codes.
Shield Termination - SHLD
The SHLD terminal located on the cable entry plate provides a 
grounding point for the motor cable shield. Refer to figure 5.1 for 
location. 
The motor cable shield should be connected to this terminal (drive 
end) and the motor frame (motor end). A shield-terminating cable 
gland may so be used.
When shielded cable is used for control and signal wiring, the 
shield should be grounded at the source end only, not at the drive 
end.
RFI Filter Grounding
Using an optional RFI filter may result in relatively high ground 
leakage currents. Therefore, the filter must only be used in 
installations with grounded AC supply systems and be 
permanently installed and solidly grounded (bonded) to the 
building power distribution ground. Ensure that the incoming supply 
neutral is solidly connected (bonded) to the same building power 
distribution ground. Grounding must not rely on flexible cables and 
should not include any form of plug or socket that would permit 
inadvertent disconnection. Some local codes may require 
redundant ground connections. The integrity of all connections 
should be periodically checked.