Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 169

Advertising
background image

Parameter Descriptions

12-39

Sets the current limit value when Current Lmt Sel (147) = Cur Lim
Val.

Sets the responsiveness of the current limit.

Selects the drive’s response to increasing drive temperature. The
drive could reduce current limit, PWM carrier, or both. A fault or
alarm will also be activated when an overload is detected.

Sets the carrier frequency for the PWM output. Drive derating may
occur at higher carrier frequencies. For derating information, refer to
Appendix A.

148

Current Lmt Val

Range:

Based on Drive Type [0.1 Amps]

Default:

Based on Drive Type (approximately 150% of Drive
Rated Amps)

Access:

0

Path: Dynamic Control>Load Limits

See also:

147, 149

149

Current Lmt Gain

Range:

0 to 5000 [1]

Default:

200

Access:

2

Path: Dynamic Control>Load Limits

See also:

147, 148

150

Drive OL Mode

Range:

0 = Disabled
1 = Reduce CLim
2 = Reduce PWM
3 = Both-PWM 1st

Default:

3 = Both-PWM 1st

Access:

1

Path: Dynamic Control>Load Limits

See also:

219

151

CarrierFrequency

Range:

2 - 10 kHz [1 kHz]

Default:

4 kHz

Access:

0

Path: Dynamic Control>Load Limits

See also:

146, 149