Parameter Descriptions

12-55

Enables/disables the feature that saves the present MOP
(motor-operated potentiometer) frequency reference at power down
and/or at stop. If the drive is re-started or powered up, the setpoint
will be restored with the last active MOP output value.

Important:

The MOP feature requires that the digital inputs be
configured for MOP Inc and MOP Dec (see 361-366).

Sets the rate of change of the MOP reference in response to a
digital input.

194

Save MOP Ref

Range:

See figure 12.26

Default:

See figure 12.26

Access:

2

Path: Utility>MOP Config

See also:

Figure 12.26 – Save MOP Ref (194)

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

At Stop

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Figure 12.27 – Configuring Digital Inputs for MOP Inc and MOP Dec

Dig In #

Dig In #

Dig In #

Dig In #

+24 V

MOP Inc

MOP Dec

195

MOP Rate

Range:

0.2 to Maximum Freq [0.1 Hz/sec]

Default:

1.0 Hz/sec

Access:

2

Path: Utility>MOP Config

See also: