Parameter Descriptions
12-55
Enables/disables the feature that saves the present MOP
(motor-operated potentiometer) frequency reference at power down
and/or at stop. If the drive is re-started or powered up, the setpoint
will be restored with the last active MOP output value.
Important:
The MOP feature requires that the digital inputs be
configured for MOP Inc and MOP Dec (see 361-366).
Sets the rate of change of the MOP reference in response to a
digital input.
194
Save MOP Ref
Range:
See figure 12.26
Default:
See figure 12.26
Access:
2
Path: Utility>MOP Config
See also:
Figure 12.26 – Save MOP Ref (194)
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Save
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At P
owr Do
wn
At Stop
Nibble 1
Nibble 2
Nibble 3
Nibble 4
Figure 12.27 – Configuring Digital Inputs for MOP Inc and MOP Dec
Dig In #
Dig In #
Dig In #
Dig In #
+24 V
MOP Inc
MOP Dec
195
MOP Rate
Range:
0.2 to Maximum Freq [0.1 Hz/sec]
Default:
1.0 Hz/sec
Access:
2
Path: Utility>MOP Config
See also: