Parameter Descriptions

12-85

Selects whether the signed value or absolute value of a parameter
is used before being scaled to drive the analog output. See
parameter 343 for specific signals that can be output.

Selects the source of the value that drives the analog output. The
analog output can be a voltage (0-10 VDC) signal connected to
terminals 22 and 23. See also Table 12.4.

341

Anlg Out Absolut

Range:

See figure 12.52

Default:

See figure 12.52

Access:

2

Path: Inputs & Outputs>Analog Outputs

See also:

342

Figure 12.52 – Anlg Out Absolute (341)

Bit

Signal Level

Output Volts

0

-100%
0%
100%

0 V
5 V

10 V

1

-100%
0%
100%

10 V

0 V

10 V

x

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Absolute
0 =Signed
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

Enabled: Signal output range 0 to10 VDC.
Disabled: Based output at 5 VDC for 0% output signal.

342

Analog Out1 Sel

Range:

0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = Post Rmp Ref

Default:

0 = Output Freq

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

1 - 7, 12, 135 - 138, 219, 220, 343