SP600 AC Drive User Manual
Analog Input 2, 
Differential Current Input
 Signal level
 Differential Input resistance
 Isolation
 Initial accuracy (@25°C)
 Resolution
 Common Mode Rejection Ratio
 Input processing period
 Terminal block size
Protection
0(4)-20mA
100
Ω
±165V
±0.3%
10 bits (0.1%)
70dB up to 500Hz over temp range
5ms
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
ESD protected (6 kV contact 
discharge, 8 kV air discharge)
Analog Output
 Analog output voltage range
 Loading impedance
 Accuracy over temperature range
 Resolution
 Frequency of output waveform
 Output processing period
 Terminal block size
Protection
0 to +10V
2k
Ω minimum
±2.35% maximum
10 bits (0.1%)
160Hz maximum
5ms
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
Short circuit proof, ESD protected 
(6 kV contact discharge, 8 kV air 
discharge)
Reference Power Supply
 Output Voltage
 Potentiometer resistance range
 Accuracy over temperature range
 Terminal block size
Protection
10V
2k
Ω to 10kΩ
±2.35% maximum
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
Short circuit proof, ESD protected 
(6 kV contact discharge, 8 kV air 
discharge)
24V Power Supply
 Output Voltage
 Output Current
 Isolation
 Terminal block size
Protection
24V to 28V
150mA maximum 
±25V
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
Short circuit proof, ESD protected 
(6 kV contact discharge, 8 kV air 
discharge)