Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 224

Advertising
background image

12-94

SP600 AC Drive User Manual

28 = PI Reset: If this input function is closed, the integrator for the
Process PI loop will be reset to 0.

If this input function is open, the integrator for the Process PI loop
will integrate normally.

29-38 = Reserved

39 = UserSetBit0

40 = UserSetBit1

If either UserSetBit0 or UserSetBit1 is not defined, a zero
value is used in place of the input to determine which User
Set is loaded, while Dynamic Mode is enabled. These bits
only affect the drive when Dynamic Mode (204) is active. See
table 12.9.

Type 2 Alarms

Some digital input programming may cause conflicts that result in a
Type 2 alarm. For example, Digital In1 Sel set to 5 (Start) in 3-wire
control, and Digital In2 Sel set to 7 (Run) in 2-wire control. These
alarms prevent the drive from starting. Refer to chapter 13 for more
information about these alarms. Dig In Status (116) indicates the
current state of the digital inputs.

Table 12.9 – Dynamic User Mode

Dynamic User Set Mode

UserBit1

UserBit0

User Set Loaded In Memory

0

0

User Set 1

0

1

User Set 2

1

0

User Set 3

1

1

User Set 3

Advertising