Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 148
 
12-18
SP600 AC Drive User Manual
Sets the method of speed regulation. See figure 12.6.
0 = Open Loop provides no speed compensation due to load 
variations. This is strict volts per hertz output as a function of the 
speed reference.
1 = Slip Comp provides for frequency output adjustment as a 
function of load. The amount of compensation is defined by the 
value of Slip RPM @ FLA.
2 = Process PI allows for the output motor speed (frequency) to be 
adjusted based on the outer control loop regulator.
Sets the low limit for the speed reference after scaling is applied. 
See figure 12.7.
80
Speed Mode
Range:
0 = Open Loop
1 = Slip Comp
2 = Process PI
Default:
0 = Open Loop
Access:
2
Path: Speed Command>Spd Mode & Limits
See also:
124 -138
Figure 12.6 – Speed Control Method
+
Spd Cmd
Process PI
Controller
Linear Ramp
& S-Curve
+
+
+
PI Disabled
Speed Control
Spd Ref
PI Ref
PI Fbk
Slip Adder
Open
Loop
Slip
Comp
Process
PI
81
Minimum Speed
Range:
0.0 to Maximum Speed [0.1 Hz]
Default:
0.0 Hz
Access:
0
Path: Speed Command>Spd Mode & Limits
See also:
83, 92, 95
!
ATTENTION: The drive can operate at and maintain 
zero speed. The user is responsible for assuring safe 
conditions for operating personnel by providing 
suitable guards, audible or visual alarms, or other 
devices to indicate that the drive is operating or may 
operate at or near zero speed. Failure to observe 
this precaution could result in severe bodily injury or 
loss of life.