12-14

SP600 AC Drive User Manual

Enables/disables the compensation correction options.

Bit 0 - Reflect Wave

• Enables/disables reflected wave correction software, which

reduces overvoltage transients from the drive to the motor. For
lead lengths beyond 300 feet, enable this feature.

Bit 1 - Enable Jerk

• Enables/disables the jerk limit in the current limiter that helps to

eliminate overcurrent trips on fast accelerations. Disable this
feature if your application requires the actual acceleration of the
motor to be faster than .25 sec.

Flux-up current is the amount of DC current equal to current limit so
that full flux can be established in the motor prior to acceleration.

0 = Manual: Flux is established for Flux Up Time (58) before
acceleration. The flux-up time can be a user value set in parameter
58.

1 = Auto: Flux is established for a calculated time period based on
motor nameplate data. Flux Up Time (58) is not used.

56

Compensation

Range:

See figure 12.5

Default:

See figure 12.5

Access:

2

Path: Motor Control>Torq Attributes

See also:

Figure 12.5 – Compensation (56)

1

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Reflect W

av

e

Enab

le Jer

k

Nibble 1

Nibble 2

Nibble 3

Nibble 4

57

Flux Up Mode

Range:

0 = Manual
1 = Automatic

Default:

0 = Manual

Access:

2

Path: Motor Control>Torq Attributes

See also:

53, 58