3-4

SP600 AC Drive User Manual

3.1.1.2 Input Power Conditioning

Certain events on the power system supplying a drive can cause
component damage or shortened product life. These conditions are
divided into two basic categories:

All Drives

The power system has power factor correction capacitors
switched in and out of the system either by the user or by the
power company.

The power source has intermittent voltage spikes in excess of
6000 volts. These spikes could be caused by other equipment on
the line or by events such as lightning strikes.

The power source has frequent interruptions.

Table 3.1 – MOV and Common Mode Capacitor Jumpers

Frame

Jumper

Removes

A

N/A

B

JP6-JP5

Common Mode Capacitors to Ground

C and D

JP3B – JP3A

Common Mode Capacitors to Ground

E

JP3 – JP4

Common Mode Capacitors to Ground

DC+

DC–

Converter

Common

Mode

Capacitors

See Chart

Figure 3.2 – Phase-to-Ground MOV Removal

Jumper JP3-JP2 removes MOV to Ground (Frames A - D)

Jumper JP1-JP2 removes MOV to Ground (Frame E)

R
S
T

1

2

3

4

Three-Phase

AC Input

See Chart