Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 41
Mounting the Drive
3-3
3.1.1.1 Unbalanced or Ungrounded Distribution Systems
To disconnect the MOVs and common mode capacitors, remove the 
jumper(s) shown in figures 3.1 and 3.2 and table 3.1. 
!
ATTENTION: SP600 drives contain protective MOVs and 
common mode capacitors that are referenced to ground. To 
guard against drive damage, these devices should be 
disconnected if the drive is installed on an ungrounded 
distribution system where the line-to-ground voltages on any 
phase could exceed 125% of the nominal line-to-line voltage. 
Failure to observe this precaution could result in damage to, 
or destruction of, the equipment.
ATTENTION: To avoid electric shock hazard, verify that the 
voltage on the bus capacitors has discharged before 
removing/installing jumpers. Measure the DC bus voltage at 
the +DC terminal of the Power Terminal Block and the -DC 
test point. The voltage must be zero.
Figure 3.1 – Typical Jumper Locations (C Frame Shown)
JP3
JP2
JP3A
JP3B