The functions below can be controlled via digital input selection
functions (361-366):

Bit 0 - PI Enable

• Enables/disables the operation of the PI loop.

Bit 1 - PI Hold

• Enabled = The integrator for the outer control loop is held at

the current level; that is, it will not increase.

• Disabled = The integrator for the outer PI control loop is

allowed to increase.

Bit 2 - PI Reset

• Enabled = The integrator for the outer PI control loop is reset

to zero.

• Disabled = The integrator for the outer PI control loop

integrates normally.