Troubleshooting the Drive

13-17

13.5

Test Point Codes and Functions

Table 13.7 – Fault Names Cross-Referenced by Fault Number

No.

1

Fault

No.

1

Fault

No.

1

Fault

2

Function Loss

38

Phase U to Grnd

79

Excessive Load

3

Power Loss

39

Phase V to Grnd

80

AutoTune Aborted

4

UnderVoltage

40

Phase W to Grnd

81-86 Port 1-6 DPI Loss

5

OverVoltage

41

Phase UV Short

100

Parameter Chksum

7

Motor Overload

42

Phase VW Short

101

UserSet1 Chksum

8

Heatsink OvrTemp

43

Phase UW Short

102

UserSet2 Chksum

9

Trnsistr OvrTemp

48

Params Defaulted

103

UserSet3 Chksum

12

HW OverCurrent

63

Shear Pin

104

Pwr Brd Chksum1

13

Ground Fault

64

Drive Overload

105

Pwr Brd Chksum2

24

Decel Inhibit

69

DB Resistance

106

Incompat MCB-PB

25

OverSpeed Limit

70

Power Unit

107

Replaced MCB-PB

29

Analog In Loss

71-76 Port 1-6 Net Loss

108

Anlg Cal Chksum

33

Auto Rstrt Tries

77

IR Volts Range

36

SW OverCurrent

78

FluxAmpsRef Rang

1

Fault numbers not listed are reserved for future use.

Table 13.8 – Test Point Codes and Functions

Code Selected in

Testpoint x Sel (234, 236)

Function Whose Value is Displayed

in Testpoint x Data (235, 237)

1

DPI Error Status

2

Heatsink Temperature

3

Active Current Limit

4

Active PWM Frequency

5

Lifetime MegaWatt Hours

1

1

Use the equatio

n

below to calculate total Lifetime MegaWatt Hours.

6

Lifetime Run Time

7

Lifetime Powered Up Time

8

Lifetime Power Cycles

9

Life MegaWatt Hours Fraction

1

10

Life MegaWatt Hours Fraction Units

1

11-99

Reserved for Factory Use

Value of Code 9

Value of Code 10

---------------------------------

0.1

×

Value of Code 5

+

Total Lifetime MegaWatt Hours

=