Troubleshooting the Drive

13-15

Port 1-6 Net
Loss

71-

76

The network module
connected to DPI port
stopped
communicating.

The fault code indicates
the offending port
number (71 = port 1,
etc.)

1. Check communication

module for proper
connection to external
network.

2. Check external wiring to

module on port.

3. Verify external network

fault.

Power Loss

3

DC bus voltage
remained below 85% of
nominal for longer than
Power Loss Time (185).

Enable/disable with
Fault Config 1 (238).

Monitor the incoming AC
line for low voltage or line
power interruption.

Power Unit

70

One or more of the
output transistors were
operating in the active
region instead of
desaturation. This can
be caused by excessive
transistor current or
insufficient base drive
voltage.

1. Check for damaged

output transistors.

2. Replace drive.

Pwr Brd
Chksum1

104

The checksum read
from the EEPROM does
not match the checksum
calculated from the
EEPROM data.

Clear the fault or cycle
power to the drive.

Pwr Brd
Chksum2

105

The checksum read
from the board does not
match the checksum
calculated.

1. Cycle power to the

drive.

2. If problem persists,

replace drive.

Replaced
MCB-PB

107

Main Control board was
replaced and
parameters were not
programmed.

1. Restore defaults.

2. Reprogram parameters.

Shear Pin

63

Programmed Current
Lmt Val (148) has been
exceeded.
Enabled/disable with
Fault Config 1 (238).

Check load requirements
and Current Lmt Val (148)
setting.

Table 13.6 – Fault Descriptions and Corrective Actions (Continued)

Fault

No.

Ty

p

e

Description

Action