Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 153
 
Parameter Descriptions
12-23
Selects the source of the speed reference to the drive unless Preset 
Speed 1-7 (101-107)
is selected.
Note that the manual mode select and logic select of OIM Control 
can override the reference control source. See figure 12.10.
90
Speed Ref A Sel
Range:
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = Reserved
22 = Network
23 = Reserved
Default:
18 = Local OIM
Access:
0
Path: Speed Command>Speed References
 Speed Command>Control Src Select
See also:
2, 91-92, 101-107, 117-120, 192-194, 213, 272, 273, 
361-366, 320-327
!
ATTENTION: Removing and replacing the LCD OIM 
while the drive is running may cause an abrupt speed 
change if the LCD OIM is the selected reference 
source, but is not the selected control source. The 
drive will ramp to the reference level provided by the 
OIM at the rate specified in Accel Time 1 (140), Accel 
Time 2 (141), Decel Time 1 (142) and Decel Time 2 
(143). Be aware that an abrupt speed change may 
occur depending upon the new reference level and 
the rate specified in these parameters. Failure to 
observe this precaution could result in bodily injury.