Parameter Descriptions

12-19

Sets the high limit for the speed reference after scaling is applied.
See figure 12.7.

Sets the incremental amount of the output frequency (above
Maximum Speed) allowable for functions such as slip
compensation. See figure 12.7.

Maximum Speed (82) + Overspeed Limit (83) must be

≤ to Maximum Frequency (55)

82

Maximum Speed

Range:

5.0 to 400.0 Hz [0.0 Hz]

Default:

50.0 or 60.0 Hz (dependent on voltage class)

Access:

0

Path: Speed Command>Spd Mode & Limits

See also:

55, 83, 91, 202

!

ATTENTION: The user is responsible for ensuring
that driven machinery, all drive-train mechanisms,
and application material are capable of safe
operation at the maximum operating speed of the
drive. Overspeed detection in the drive determines
when the drive shuts down.

See figure 12.7

.

Failure

to observe this precaution could result in bodily
injury.

83

Overspeed Limit

Range:

0.0 to 20.0 Hz [0.1 Hz]

Default:

10.0 Hz

Access:

2

Path: Speed Command>Spd Mode & Limits

See also:

55, 82

Figure 12.7 – Speed Limits

Allowable Output Frequency Range

Bus Regulation or Current Limit

V

o

l

t

a

g

e

Frequency

Allowable Output Frequency Range

Normal Operation

Allowable Reference Frequency Range

Frequency Trim due to
Speed Control Mode

Max Volts

Motor Volts

Break Volts

Start Boost

Run

0

Min

Speed

Motor

Hz

Max

Speed

Output

Freq Limit

Max
Freq

Break

Frequency

Overspeed

Limit