Sets the reaction to a loss of input power. Power loss is recognized 
when:
• DC bus voltage is
≤ 73% of DC Bus Memory and Power Loss
Mode is set to Coast.
• DC bus voltage is
≤ 82% of DC Bus Memory and Power Loss
Mode is set to Decel.
0 = Coast: The drive coasts to stop if the bus voltage drops below 
the threshold level. (Output transistors disabled.)
1 = Decel: Provides inertia ride-through, which may prevent the 
drive from the need to reconnect to the motor. By recapturing the 
mechanical energy, converting it to electrical energy, and returning it 
to the drive, the bus voltage is maintained. As long as there is 
mechanical energy, the ride-through time is extended, and the 
motor remains fully fluxed up. If AC input power is restored, the 
drive can ramp the motor to the correct speed without the need for 
reconnecting.
Sets the time that the drive will remain in power loss mode before a 
fault is issued.
184
Power Loss Mode
Range:
0 = Coast
1 = Decel
Default:
0 = Coast
Access:
1
Path: Dynamic Control>Stop/Power Loss
See also:
185
185
Power Loss Time
Range:
0.0 to 60.0 Sec [0.1 Sec]
Default:
0.5 Sec
Access:
1
Path: Dynamic Control>Stop/Power Loss