Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 29
 
About the Drive
2-15
is running, the transfer of the selected User Set data will not occur 
until the drive is stopped, assuming that the Dynamic Mode and the 
transfer command are both still active when the drive stops. A 
Dynamic Mode command from the user set select parameter (205) 
while the drive is running will be immediately rejected.
Typical Setup / Operation:
Step 1.
While in normal mode (Dyn UserSet Cnfg (204) = x0), 
enter data into drive and save to User Set using Save to 
User Set (199). Repeat for each needed User Set. Check 
that Dynamic User Set related Digital Inputs (parameters 
361-366) and Datalink Inputs (parameters 300-307) are 
programmed the same in each. 
Step 2.
Enable Dynamic User Set Mode (Dyn UserSet Cnfg (204) 
= x1).
Step 3.
Test restoring each programmed user Set via digital 
Inputs or DynUsrSetSel (205). If a Fault or Type 2 Alarm 
occurs (Drive Alarm 2 (212) is non-zero), the User Set 
causing the error is loaded (see Dyn UserSet Actv (206) 
for indication). Return to Normal Mode (Dyn UserSet Cnfg 
(204) = x0), correct the Digital Input or Datalink 
definition(s), and save to the User Set that was loaded. 
Repeat step 2.
Step 4.
Begin normal drive operation. Remember that User Sets 
can only be loaded while the drive is stopped. 
At power-up, the drive will load operating memory with the values 
contained in the active non-volatile storage as part of initialization. If 
Dynamic Mode is Enabled, the selected User Set data will be 
loaded and processed after drive initialization completes but before 
the drive is allowed to become active. If Dynamic Mode is active and 
drive power is removed, User Set data will not be saved and any 
parameter changes will be lost. 
When Dyn UserSet Cnfg (204) is set to Enabled, the drive will 
immediately transfer the selected User Set to operating memory as 
determined by digital inputs or DynUsrSetSel (205). The drive will 
verify that the User Set digital input configuration is identical in all 
three sets. 
To avoid operational conflict between User Set values, all digital 
inputs must be set identically in each user set. If the digital inputs in 
each user set are not set identically, a Type 2 alarm is generated. 
The condition(s) must be corrected before the drive can become 
active.
Load Frm Usr Set (198) and Save to User Set (199) commands are 
not permitted in Dynamic Mode because these operations define 
data transfer between the active memory and the User Sets.