Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 245
 
Troubleshooting the Drive
13-13
HW 
OverCurrent
12
The drive output current 
has exceeded the 
hardware current limit.
Check programming. 
Check for excess load, 
improper DC boost setting, 
DC brake volts set too high 
or other causes of excess 
current.
Motor dynamics cannot be 
accommodated by 
autotuning. Manual tuning 
of the current loop 
required. Diagnostic Item 
#51 may need to be 
reduced. Consult technical 
support.
Incompat 
MCB-PB
106
Drive rating information 
stored on the power 
board is incompatible 
with the Main Control 
board.
Load compatible version 
files into drive.
IR Volts 
Range
77
The drive autotuning 
default is Calculate and 
the value calculated for 
IR Drop Volts is not in 
the range of acceptable 
values.
Re-enter motor nameplate 
data.
Motor 
Overload
7
Internal electronic 
overload trip.
Enable/disable with 
Fault Config 1 (238).
An excessive motor load 
exists. Reduce load so 
drive output current does 
not exceed the current set 
by Motor NP FLA (42).
OverSpeed 
Limit
25
Functions such as slip 
compensation or bus 
regulation have 
attempted to add an 
output frequency 
adjustment greater than 
that programmed in 
Overspeed Limit (83).
Remove excessive load or 
overhauling conditions or 
increase Overspeed Limit 
(83).
Table 13.6 – Fault Descriptions and Corrective Actions (Continued)
Fault
No.
Ty
p
e
Description
Action