4-12

SP600 AC Drive User Manual

Table 4.7 – SP600 600 VAC Input Recommended Protection Devices

Model

Number

HP

Dual Element

Time Delay

Fuse

Non-time

Delay Fuse

Circuit

Breaker

1

1

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum

ND

HD

Min

2

2

Minimum protection device size is the lowest rated device that supplies maximum
protection without nuisance tripping.

Max

3

Min

2

Max

3

3

Maximum protection device size is the highest rated device that supplies drive protection.
For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

Max

4

4

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

6SP501-0P9

0.5

0.33

3

3

3

3.5

15

6SP501-1P7

1

0.75

3

6

3

6

15

6SP501-2P7

2

1.5

4

6

4

10

15

6SP501-3P9

3

2

6

8

6

15

15

6SP501-6P1

5

3

10

12

10

20

20

6SP501-9P0

7.5

5

10

20

10

35

35

6SP501-011

10

7.5

15

20

15

40

40

6SP501-017

15

10

20

35

20

60

60

6SP501-022

20

15

25

45

25

80

80

6SP501-027

25

20

35

60

35

100

100

6SP501-032

30

25

40

70

40

125

125

6SP501-041

40

30

50

90

50

150

150

6SP501-052

50

40

60

110

60

200

200