Parameter Descriptions

12-7

Displays the setpoint value of the signal at the MOP
(Motor-Operated Potentiometer) function. The setpoint can be
retained after power down or stop by setting parameter 194.

Displays the present DC bus voltage level.

Displays a six-minute average of the DC bus voltage level.

Displays the value of the signal at the analog inputs. This value
does not include user-programmed scaling information (for
example, Analog In1 Hi). The value displayed depends on the
setting of Analog In Config (320).

11

MOP Frequency

Range:

+/- 400.0 [0.1 Hz]

Default:

Read Only

Access:

1

Path: Monitor>Metering

See also:

194, 195

12

DC Bus Voltage

Range:

Voltage rating-dependent [0.1 VDC]

Default:

Read Only

Access:

1

Path: Monitor>Metering

See also:

13

DC Bus Memory

Range:

Voltage rating-dependent [0.1 VDC]

Default:

Read Only

Access:

2

Path: Monitor>Metering

See also:

16
17

Analog In1 Value
Analog In2 Value

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]

Default:

Read Only

Access:

1

Path: Monitor>Metering

See also:

320

Value of:

If Parameter 320

=.xx00

If Parameter 320 =

.xx11

Analog In1

volts (terminals 14/15)

mA (terminals 16/17)

Analog In2

volts (terminals 18/19)

mA (terminals 20/21)