A-4

SP600 AC Drive User Manual

Table A.4 – Electrical

Voltage Tolerance

See table A.10 for Full Power and
Operating Range.

Frequency Tolerance

47 to 63 Hz

Input Phases

Three-phase input provides full rating
for all drives. Single-phase operation
provides 50% of rated current.

Displacement Power Factor

0.98 across speed range

Efficiency

97.5% at rated amps, nominal line volts.

Maximum Short Circuit Rating

200,000 amps symmetrical.

Actual Short Circuit Rating

Determined by amps interrupting
capacity (AIC) rating of installed
fuse/circuit breaker.

Table A.5 – Control

Method

Sine-coded PWM with programmable carrier
frequency. Ratings apply to all drives. The drive
can be supplied as 6-pulse or 12-pulse in a
configured package.

Carrier Frequency
A to D Frame Drives

2, 4, 8, and 10 kHz. Drive rating based on 4 kHz.

Output Voltage Range

0 to rated motor voltage

Output Frequency Range 0 to 400 Hz.

Frequency Accuracy

Digital Input
Analog Input

Within

±0.01% of set output frequency.

Within

±0.4% of maximum output frequency.

Selectable Motor Control

Sensorless vector with full tuning. Standard
V/Hz with full custom capability.

Speed Regulation: Open
Loop with Slip
Compensation

+/-0.5% of base speed across a 40:1 speed
range.

Stop Modes

Multiple programmable stop modes including
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S-curve.

Accel/Decel

Two independently programmable accel and
decel times. Each time may be programmed
from 0 to 3600 seconds in 0.1 second
increments.

Intermittent Overload

110% overload capability for up to 1 minute.
150% overload capability for up to 3 seconds.

Current Limit Capability

Proactive Current Limit programmable from 20
to 160% of rated output current. Independently
programmable proportional and integral gain.