Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 267
 
Technical Specifications
A-7
Six Digital Inputs
 Input voltage
 Logic thresholds
 Input resistance
 Isolation
 Assertion response (hardware only)
 Negation response (hardware only)
 Terminal block size
Protection
24V (nominal)
logic 0: V
in
< 3.2V;
logic 1: V
in
> 19.2V
2k
Ω
±25V
9ms maximum
1ms maximum
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
Short circuit proof, ESD protected 
(6 kV contact discharge, 8 kV air 
discharge)
Two Form C Relay Outputs
 Maximum Contact Voltage
 Contact rating for resistive
 loads
 Contact switching for resistive loads
 Contact rating for inductive loads
 Contact switching for inductive loads
 Isolation test voltage
 Terminal block size
Protection
250VAC, 220VDC
0.40 A at 125 VAC, 2 A at 30 VDC
50 VA, 60 W
0.20 A at 125 VAC, 1 A at 30 VDC
25 VA, 30 W
1900VDC for one minute
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
Short circuit proof, ESD protected
(6 kV contact discharge, 8 kV air 
discharge)
Table A.6 – Control Inputs, Outputs, and Power Supplies (Continued)