Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 267

Advertising
background image

Technical Specifications

A-7

Six Digital Inputs
Input voltage
Logic thresholds

Input resistance
Isolation
Assertion response (hardware only)
Negation response (hardware only)
Terminal block size

Protection

24V (nominal)
logic 0: V

in

< 3.2V;

logic 1: V

in

> 19.2V

2k

±25V
9ms maximum
1ms maximum
0.05 mm

2

to 1.5 mm

2

(30 AWG to

16 AWG)
Short circuit proof, ESD protected
(6 kV contact discharge, 8 kV air
discharge)

Two Form C Relay Outputs
Maximum Contact Voltage
Contact rating for resistive
loads
Contact switching for resistive loads
Contact rating for inductive loads
Contact switching for inductive loads
Isolation test voltage
Terminal block size

Protection

250VAC, 220VDC
0.40 A at 125 VAC, 2 A at 30 VDC

50 VA, 60 W
0.20 A at 125 VAC, 1 A at 30 VDC
25 VA, 30 W
1900VDC for one minute
0.05 mm

2

to 1.5 mm

2

(30 AWG to

16 AWG)
Short circuit proof, ESD protected
(6 kV contact discharge, 8 kV air
discharge)

Table A.6 – Control Inputs, Outputs, and Power Supplies (Continued)